Setting

Display

WARM WEATHER SHUT DOWN
Set the outdoor air temperature at which heating is
suspended during the event.

Access Level: Installer

Range: CTRL (control), 40 to
100°F (4.5 to 38.0°C), OFF

Conditions: An outdoor sensor must be available
and Schedules are in use or Scenes is set to All or
Guest.

Default: CTRL

SET COOL ROOM
Set the room cooling temperature for the event.

Access Level: Installer, User

Range: 50 to 100°F (10.0 to
38.0°C)

Conditions: Always

Default: 78°F (25.5°C)

SET COOL ROOM
Set the room cooling temperature for the event.

Access Level: Installer, User

Range: 50 to 100°F (10.0 to
38.0°C)

Conditions: Requires that Schedules are in use or
Scenes is set to All or Guest.

Default: 85°F (29.5°C)

SET COOL ROOM AWAY
Set the room cooling temperature during the Away
scene.

Access Level: Installer

Range: 50 to 100°F (10.0 to
38.0°C)

Conditions: Scenes is set to Away, All or Guest.

Default: 85°F (29.5°C)

COOL MINIMUM ROOM LIMIT
Set the minimum room cooling limit while in the

event.

Access Level: Installer

Range: 50 to 100°F (10.0 to
38.0°C)

Conditions: Always available.

Default: 50°F (10.0°C)

COOL MINIMUM ROOM LIMIT
Set the minimum room cooling limit while in the

event.

Access Level: Installer

Range: 50 to 100°F (10.0 to
38.0°C)

Conditions: Always available.

Default: 50°F (10.0°C)

Set Temp Menu (2 of 4)