Toolbox Menu (3 of 3)

Setting

Display

DEVICE COUNT
Provides a count of all the tekmarNet

®

thermostats and

setpoint controls on the tekmarNet

®

system.

Access Level: Installer

Range: 1 to 24

Conditions: Must be connected to a tekmarNet

®

system.

Default: 1

USER TEST
Use the up or down arrow keys to select either the heat or
cool test sequence, then press the NEXT key to begin. Press
HOLD to pause at step for 5 minutes. Press NEXT to advance
to the next step.

Access Level: Installer

Range: OFF, HEAT or
COOL

Conditions: Always available.

Default: OFF

OFFSET ROOM
Manual offset correction of the room temperature
measurement.

Access Level: Installer

Range: -5 to +5°F (-3.0 to
+3.0°C)

Conditions: Always available.

Default: 0°F (0.0°C)

OFFSET HUMIDITY
Manual of fset c orrec tion of the room humidit y
measurement.
Access Level: Installer

Range: -10 to +10%

Conditions: Always available.

Default: 0%

FILTER CHANGE HOURS
Select the amount of time the fan operates before the air filter
requires maintenance.

Access Level: Installer

Range: OFF, 200 to 2000
hours

Conditions: Always available.

Default: OFF

LOAD FACTORY DEFAULTS
Touch Enter to load the factory defaults settings.

Access Level: Installer

Range: None

Conditions: Always available.

Default: Keep existing
settings

ERROR HISTORY 1 THROUGH 5
Displays a history of the last 5 errors that have occurred on
the thermostat in the past 30 days. Touch Enter to manually
clear the error code.

Access Level: Installer

Range: See
Troubleshooting section

Conditions: An error must have occurred.

Default: Not applicable