Setting

Display

COOL MAXIMUM ROOM LIMIT
Set the maximum room cooling limit.

Access Level: Installer

Range: 50 to 100°F (10.0 to
38.0°C)

Conditions: Always available

Default: 100°F (38.0°C)

FLOOR MINIMUM
Set the floor heating temperature while in the
event.

Access Level: Installer, User

Range: OFF, 40 to 122°F (4.5 to
50.0°C)

Conditions: Sensor 1, 2 or 3 is set to Floor, and W1
Terminal is set to HRF1, HRF2 or Othr.

Default: 72°F (22.0°C)

FLOOR MINIMUM
Set the floor heating temperature while in the
event.

Access Level: Installer, User

Range: OFF, 40 to 122°F (4.5 to
50.0°C)

Conditions: Sensor 1, 2 or 3 is set to Floor, and W1
Terminal is set to HRF1, HRF2 or Othr, & Schedules
are in use or Scenes are set to All or Guest.

Default: OFF

FLOOR MAXIMUM
Set the floor maximum temperature in order to
protect the floor covering.
Suggested settings: Tile = 90°F (32°C)
Hardwood Floor = 85°F (29°C)

Access Level: Installer

Range: 40 to 122°F (4.5 to
50.0°C), OFF

Conditions: Sensor 1, 2 or 3 is set to Floor, & W1
Terminal is set to HRF1, HRF2 or Othr.

Default: 85°F (29.5°C)

TEMPORARY HOLD
Temperature adjustment in the home menu
can result in either permanent temperature
setting change or temporary temperature setting
change that lasts 3, 6, 9, 12 hours or until the
next scheduled event.
Access Level: Installer

Range: OFF or ON

Conditions: None

Default: OFF

Set Temp Menu (3 of 4)