4. If the thermostat display is off, or is cycling on and off, move the thermostat to the

next available zone on the House Control, Wiring Center, or Zone Manager.

If the thermostat display remains permanently on, there may be a fault with the
previously tried zone on the House Control, Wiring Center, or Zone Manager.
If the thermostat display continues to be off, or is cycling on and off, there may
be a fault on the thermostat.

If a fault is suspected, contact your tekmar sales representative for assistance.

Testing tekmarNet

®

4 and Stand Alone Wiring

--------------------------

--------------------------

Testing the Power
1. Remove the front cover from the thermostat.
2. Use an electrical test meter to measure (ac) voltage between the R and C terminals.

The reading should be 24 V (ac) +/– 10%.

3. Install the front cover.

Testing the Relay Outputs

--------------------------------------------

--------------------------------------------

The thermostat includes a User Test to check if the thermostat’s relays are operating
and that the thermostat is wired correctly to the HVAC equipment. The User Test setting
can be located in the Toolbox menu. Either Heat or Cool test can be selected.
Cancel button - Exits the user test and returns the Toolbox menu.
Hold button - Pauses the user test step for up to 5 minutes.
Next Item button - Advances the user test to the next test step.

User Test Sequence

Heat Test

Cool Test

Step

Relay(s) Closed

Step

Relay(s) Closed

O Relay OFF

Rc-O/B is opened

O Relay ON

Rc-O/B

B Relay ON

Rc-O/B

B Relay OFF

Rc-O/B is opened

Fan

Rc-G

Fan

Rc-G

Y1 Heat

Rc-Y1 and Rc-G

Y1 Cool

Rc-Y1 and Rc-G

Y2 Heat

Rc-Y1 and Rc-Y2 and
Rc-G

Y2 Cool

Rc-Y1 and Rc-Y2 and
Rc-G

W2 Heat

Rh2-W2

W2 Cool

Rh2-W2

W1 Heat

Rh1-W1

Humidify*

ACC-ACC

Humidify*

ACC-ACC

Dehumidify*

ACC-ACC or Rc-Y2

Dehumidify*

ACC-ACC or Rc-Y2

HRV*

Rc-Y2

HRV*

Rc-Y2

Valve*

ACC-ACC or Rc-Y2

Valve*

ACC-ACC or Rc-Y2

*availability of test step and additional relay closures based upon Setup menu settings.