Setting

Display

HEAT Y2 HOURS
The total number of hours the second stage of heat
pump has been in heating operation. Touch the
number and the ENTER key to reset.
Access Level: Installer, User

Range: 0000 to 9999 hours

Conditions: Setup menu setting Y2 TYPE is set to
HP2.

Default: 0000 hours

HEAT W1 HOURS
The total number of hours the W1 relay has been
operated for heating. Touch the number and the
ENTER key to reset.
Access Level: Installer, User

Range: 0000 to 9999 hours

Conditions: Setup menu W1 TERM is set to HRF1,
HRF2 or OTHR.

Default: 0000 hours

BACKUP W2 HOURS
The total number of hours the Backup W2 relay has
been operated for heating. Touch the number and
the ENTER key to reset.
Access Level: Installer, User

Range: 0000 to 9999 hours

Conditions: Setup menu setting BACKUP W2 TERM
is set to CONV, COIL, FURN, or OTHR.

Default: 0000 hours

COOL Y1 HOURS
The total number of hours the first stage of heat pump
has been in cooling operation. Touch the number and
the ENTER key to reset.
Access Level: Installer, User

Range: 0000 to 9999 hours

Conditions: Always available.

Default: 0000 hours

COOL Y2 HOURS
The total number of hours the second stage of heat
pump has been in cooling operation. Touch the
number and the ENTER key to reset.
Access Level: Installer, User

Range: 0000 to 9999 hours

Conditions: Setup menu Y2 TYPE is set to HP2.

Default: 0000 hours

COOL W1 HOURS
The total number of hours the W1 relay has been
operated for cooling. Touch the number and the
ENTER key to reset.
Access Level: Installer, User

Range: 0000 to 9999 hours

Conditions: Setup menu setting Floor Cool is set to
ON and W1 TERM is set to HRF1 or HRF2.

Default: 0000 hours

Monitor Menu (4 of 5)