Setup menu (1 of 7) – tekmar 557 Thermostat Installation User Manual

Page 26

Advertising
background image

© 2014

557_D - 09/14

26 of 52

A Watts Water Technologies Company

Setup Menu (1 of 7)

Setting

Display

SENSOR 1
Select to the type of sensor connected to auxiliary
sensor input 1.

Access Level: Installer

Range: OFF, ROOM, FLOR (floor),
DUCT

Conditions: Always available.

Default: OFF

SENSOR 2
Select to the type of sensor connected to auxiliary
sensor input 2.

Access Level: Installer

Range: OFF, ROOM, FLOR (floor),
OUT (outdoor)

Conditions: Always available.

Default: OFF

SENSOR 3
Select to the type of sensor connected to auxiliary
sensor input 3.

Access Level: Installer

Range: OFF, ROOM, FLOR (floor),
HUM (humidity)

Conditions: Always available.

Default: OFF

ROOM SENSOR
Select whether the built-in room temperature sensor
is on or off.

Access Level: Installer

Range: OFF or ON

Conditions: Only available when Sensor 1, 2 or 3 is
set to ROOM or FLOR.

Default: ON

HUMIDITY SENSOR
Select whether the built-in humidity sensor is on
or off.

Access Level: Installer

Range: OFF or On

Conditions: Only available when Sensor 3 is set
to HUM.

Default: On

W1 TERMINAL UNIT
Select the terminal unit type of the first stage of
heat W1.
HRF1 = High mass hydronic radiant floor
HRF2 = Low mass hydronic radiant floor
OTHR = Other than hydronic heating

Access Level: Installer

Range: NONE, HRF1, HRF2,
OTHR

Conditions: Always available. HRF1 and HRF2 only
available when connected to a tekmarNet

®

System

Control.

Default: NONE