Congratulations on the purchase of your new tekmar

®

thermostat.

This manual will step through the complete installation, programming and sequence
of operation for this control. At the back, there are tips for control and system
troubleshooting.

Getting Started

Preparation

tekmar or jeweller screwdriver
Phillips head screwdriver


Wire Stripper

Tools Required

------------------------------------------------------

------------------------------------------------------

Materials Required

--------------------------------------------------

--------------------------------------------------

18 AWG LVT Solid Wire
(Low Voltage Connections)

Installation

Choose the placement of the thermostats early in the construction process to enable
proper wiring during rough-in.

Installation Location

-------------------------------------------------

-------------------------------------------------

Consider the following:

Interior Wall.
Keep dry. Avoid potential leakage onto the control.
Relative Humidity less than 90%. Non-condensing environment.
No exposure to extreme temperatures beyond 32-122°F (0-50°C).
No draft, direct sun, or other cause for inaccurate temperature readings.
Away from equipment, appliances, or other sources of electrical
interference.
Easy access for wiring, viewing, and adjusting the display screen.
Approximately 5 feet (1.5 m) off the finished floor.
The maximum length of wire is 500 feet (150 m).
Strip wire to 3/8" (10 mm) for all terminal connections.
Use standard 8 conductor, 18 AWG wire.










Do not use in the presence of ammonia (barn animals), methanol, ethanol
or acetone. Damage to the internal sensor may result.