Setup menu (7 of 7) – tekmar 557 Thermostat Installation User Manual

Page 32

Advertising
background image

© 2014

557_D - 09/14

32 of 52

A Watts Water Technologies Company

Setup Menu (7 of 7)

Setting

Display

AIR GROUP MASTER
Select if the thermostat is a master of an air group.

Access Level: Installer

Range: NONE, 1 to 16

Conditions: The thermostat must be connected to
other thermostats using tekmarNet

®

.

Default: NONE

PRIORITY
Select either heating or cooling priority.
Access Level: Installer

Range: HEAT or COOL

Conditions: Air Group Master is set to 1 to 16.

Default: COOL

VENTILATION MODE
Select whether the fan provides ventilation.
Access Level: Installer

Range: OFF or ON

Conditions: Always available.

Default: OFF

HEAT PURGE
Select the fan coil heating purge based upon either
time or on duct air temperature.

Access Level: Installer

Range: 0:00 to 3:00 minutes
(no duct sensor) or
70 to 160°F, OFF (21.0 to 71.0°C,
OFF) (with duct sensor)

Conditions: Always available.

Default: 0:30 min or 100°F (38.0°C)

COOL PURGE
Select the fan coil cooling purge based upon either
time or on duct air temperature.

Access Level: Installer

Range: 0:00 to 3:00 minutes
(no duct sensor) or
OFF, 40 to 70°F (OFF, 4.5 to
21.0°C) (duct sensor required)

Conditions: Always available.

Default: 0:00 min or 60°F (15.5°C)

HUMIDIFY MODE
Select the humidifier operation mode.

Access Level: Installer

Range: OFF, HM1, HM2, HM3

Conditions: ACC RELAY is set to HUM.

Default: OFF

DEHUMIDIFY MODE
Select the dehumidifier mode.

Access Level: Installer

Range: OFF, DHM1 to DHM5

Conditions: ACC RELAY is set to DHUM or Y2 RELAY
is set to DHUM or HRV.

Default: OFF