Setup Menu (5 of 7)

Setting

Display

Y2 DELAY
Select the amount of time that must elapse after the Y1
relay is turned on before the Y2 relay is allowed.

Access Level: Installer

Range: AUTO, 5 to 180 minutes

Conditions: Y2 RELAY is set to HP2 or AC2.

Defaults: AUTO minutes

COOLING CWSD
Select the outdoor temperature below which the
cooling system is disabled.

Access Level: Installer

Range: OFF, 35 to 75°F
(OFF, 1.5 to 24.0°C)

Conditions: Always available.

Default: 55°F (13.0°C)

INTERLOCK
Select the amount of time for the heat - cool interlock.
Applies only when Mode is set to Auto. Reduces
excessive heat-cool switchovers.
Access Level: Installer

Range: 10 to 180 minutes

Conditions: Always available.

Default: 30 minutes

BALANCE POINT SCHEDULE
Select if the heat pump balance point should change
based upon a programmable schedule.

Access Level: Installer

Range: OFF, ZONE, MEMBER 1
to 4

Conditions: Y1 RELAY is set to HP1 and outdoor
temperature is available.

Default: OFF

BALANCE POINT
Heat pump balance point during the time period.

Access Level: Installer

Range: OFF, 10 to 70°F
(OFF, -12.0 to 21.0°C)

Conditions: Y1 RELAY is set to HP1 and an outdoor
temperature is available.

Default: OFF

BALANCE POINT
Heat pump balance point during the time period.

Access Level: Installer

Range: OFF, 10 to 70°F (OFF,
-12.0 to 21.0°C)

Conditions: Y1 RELAY set to HP1, BALANCE POINT is set
to schedule and outdoor temperature is available.

Default: OFF