ERROR AT THERMOSTAT
There is an error on a different thermostat or setpoint control connected
to the tekmarNet

®

system and not on this thermostat.

01 to 24 = Thermostat only network
Go to the thermostat with the listed address to correct the error.

ERROR AT THERMOSTAT
There is an error on a different thermostat or setpoint control connected
to the tekmarNet

®

system and not on this thermostat.

b:01 to b:24 = boiler bus
1:01 to 1:24 = bus 1 or mix1 bus
2:01 to 2:24 = bus 2 or mix2 bus
3:01 to 3:24 = bus 3 or mix 3 bus
Go to the thermostat with the listed address to correct the error.

ERROR AT SYSTEM CONTROL
There is an error on the tekmarNet

®

system control connected to

the tekmarNet

®

system and not on this thermostat.

Error Messages (5 of 5)

Technical Data

tekmarNet

®

Thermostat 557; Radiant Floor, 2 Heat Pump/Cool, Backup, Humidity

Literature

557_A, 557_C, 557_D, 557_Q, 557_U

Control

Microprocessor control. This is not a safety (limit) control

Packaged weight

0.9 lb. (400 g)

Dimensions

4-1/2" H x 4-3/4" W x 7/8" D (114 x 120 x 22 mm)

Enclosure

White PVC plastic, NEMA Type 1

Approvals

Meets Class B: ICES & FCC Part 15

Ambient conditions Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% non-condensing

Environmental

Compatible with chlorinated swimming pool environments. Do not use
in presence of ammonia (animal barns), methanol, ethanol, acetone.

Power supply

24 V ±10%, 60 Hz, 2.0 VA standby, NEC / CEC Class 2

Relays

24 V (ac) 2 A

0-10 V (dc) Output

3.3 V (dc) humidity sensor power, 3.0 mA maximum

Humidity sensor

0 to 90% ± 3% RH

Temperature sensor NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892

– Included

None

– Optional

tekmar type # 070, 072, 073, 076, 077, 079, 083, 084, 086