Input Signal Range
Scale Input 1 Value
Scale Input 2 Value

0-50mV

000000
050000

0-100mV

000000
100000

0-1V

000000
100000

0-5V

000000
050000

1-5V

010000
050000

1-6V

010000
060000

Input Signal Range
Scale Input 1 Value
Scale Input 2 Value

0-10V

000000
100000

0-50V

000000
050000

0-100V

000000
100000

±5V

-50000

050000

±50V

-50000

050000



Table 16-2. Factory Calculated Scale Factors Table


For the purpose of this procedure, we will use an input of 0-50 mVdc and scale the meter to display 0 to 2500.0. The
calculated scale factors can now be used to scale your meter to display in engineering units using Input Scale and Offset
("IN.SC.OF") as follows:

Record your "INPUT1" and “READ 1" numbers, and your "INPUT2" and "READ 2" numbers, record them below and
proceed as follows:

Example
INPUT1 = 000000
READ 1 = 000000
INPUT2 = 050000
READ 2 = 025000


For more detail of Scale & Offset

’s examples, formulas and Calculation Table, Refer to Section 18 of MULTI-POINT

SCALE & OFFSET MENU CONFIGURATION.