3.3.5. Network management services

The network management is subdivided into two groups:
NMT services for device guarding are for boot-up, start and stop of bus users. NMT services are also
available as connection guard.


Significance of the NMT commands
The commands are transmitted as unconfirmed objects with the following structure:

Byte 0

Byte 1

Byte 2

COB-ID = 0

command byte

Node ID


COB-ID for NMT commands is always zero. The Node-ID is transmitted in byte 2 of the NMT command.


Command byte

Command byte

Meaning

State Event Mapping

01h

Start Remote Node

1

02h

Stop Remote Node

2

80h

Enter Pre-Operational Mode

3

81h, 82h

Reset Remote Node

4, 5


The Node number is the Node-ID of the requested user. Node-ID = 0 means addressing all users.


NMT State Event
After boot-up the inclination sensor is in pre-operational mode which is the state for read and write SDO
parameters. For PDO parameter requests, the inclination sensor must be set to operational mode first.

Init

Pre-Operational

Operational

Stopped/Prepared

Power on oder Hardware Reset

1

3

2

1

3

2

4/5

BootUp Message

4/5

4/5