Useful information on the sensor – Baumer GNAMG User Manual

Page 33

Advertising
background image

Manual_GNAMG_CANopen_EN.doc

33/41

Baumer IVO GmbH & Co. KG

21.11.12

Villingen-Schwenningen, Germany

SDO Abort Message
If SDO communication does not run properly, the SDO response will come with an abort code:

05040001h

: Command byte not supported

06010000h

: Incorrect object access

06010001h

: Read access on write only

06010002h

: Write access on read only

06020000h

: Object not supported

06090011h

: Subindex not supported

06090030h

: Value outside the limit

06090031h

: Value too high

08000000h

: General error

08000020h

: Incorrect saving signature ("save")

08000021h

: No data saving possible


4.3. Useful information on the sensor

Setting a new Node-ID

1. Setting a new Node-ID is by using Baumer IVO-specific object 2100h.
2. After having set the new Node-ID latter must be stored in EEPROM by object 1010h.
3. Upon next init the sensor will log in with the new Node-ID.

Setting a new baud rate

1. Setting a new baud rate is by using Baumer IVO-specific object 2101h.
2. After having set the new baud rate latter must be stored in EEPROM by object 1010h.
3. Upon next init the sensor will log in utilizing the new baud rate.
4. ! DO NOT FORGET TO ALIGN THE NEW BAUD RATE WITH MASTER!

Shield
The inclination sensor

’s base plate should always be grounded. By principle the inclination sensor should be

connected by shielded cable.
Ideally, aim at a bilateral cable shield if possible. Take care that no compensating currents are drained off the
inclination sensor.

Advertising