Configuration – Baumer GNAMG User Manual

Page 35

Advertising
background image

Manual_GNAMG_CANopen_EN.doc

35/41

Baumer IVO GmbH & Co. KG

21.11.12

Villingen-Schwenningen, Germany

Changing the baud rate
Object 2100h is for changing the baud rate. Not the real baud rate is written in the object but an index:

Baud rate

0

10 kBaud

1

20 kBaud

2

50 kBaud

3

100 kBaud

4

125 kBaud

5

250 kBaud

6

500 kBaud

7

800 kBaud

8

1000 kBaud


Now the baud rate must be saved by object 1010-1. Upon next init the inclination sensor will log in with the
new baud rate. Prior to next sensor init the baud rate of the master should be aligned.

5.2. Configuration

Changing the resolution
See object 6000h

Setting a new slope value
See objects 6112h and 6122h

Changing polarity and scaling
See objects 6111h and 6121h

Parameter saving in EEPROM
Object 1010h saves the objects below non-volatile in EEPROM. To prevent any inadvertent saving operation
the message „save“ must be written in subindex 1.

COB-ID

DLC Command

Object L

Object H Subindex Data 0

Data 1 Data 2 Data 3

600h+Node-ID

8

23h

10h

10h

01h

73 's’

61 'a’ 76 'v’ 65 'e’

COB-ID

DLC Command

Object L

Object H Subindex Data 0

Data 1 Data 2 Data 3

580h+Node-ID

8

60h

10h

10h

01h

0

0

0

0