Asynchronous Timing
In Asynchronous (Free Run) mode the encoder position data will be sampled asynchronous to the ECAT
frame. In this mode the encoder data sampling frequency (fs) is about 11 kHz. The position data sample
point may have a typical total jitter of 92µs.
The following diagram shows the relationship between data read accesses to DPRAM (from the master point
of view) at the ECAT controller and data sample and update to DPRAM from the slave (encoder).

Frame n

Frame n+1

t

Data sampling

process at slave

fs

Cylce time

(PLC Task)

Cyclic read

by master

Picture 9 Non sync (Free Run) timing diagram for a multi turn encoder

At Operating temperature = 20°C, State = OP

Name

Min

Typ

Max

Jitter (J)

0

100

µs

Cycle Time (sfc = 0/1)

1.000

64.000

µs

Table 29 Free Run timing specification for ST and MT devices

In free run mode the minimum cycle time should be larger than the maximum jitter, else the data jitter to cy-
cle time relation is poor for usual RT requirements.