General, Venting – Crestron electronic Crest Condensing Boiler 3.5 User Manual

Page 17

Advertising
background image

17

Installation & Operation Manual

Vent, air piping and termination:

The Crest vent and air piping can be installed through the roof
or through a sidewall. Follow the procedures in this manual for
the method chosen. Refer to the information in this manual to
determine acceptable vent and air piping length.

Air contamination

Pool and laundry products and common household and hobby
products often contain fluorine or chlorine compounds. When
these chemicals pass through the boiler, they can form strong
acids. The acid can eat through the boiler wall, causing serious
damage and presenting a possible threat of flue gas spillage or
boiler water leakage into the building.

Please read the information given in Table 1A, page 9,
listing contaminants and areas likely to contain them. If
contaminating chemicals will be present near the location of the
boiler combustion air inlet, have your installer pipe the boiler
combustion air and vent to another location, per this manual.

If the boiler combustion air inlet is located
in a laundry room or pool facility, for
example, these areas will always contain
hazardous contaminants.

To prevent the potential of severe personal
injury or death, check for areas and products
listed in Table 1A, page 9 before installing
the boiler or air inlet piping.

If contaminants are found, you MUST:

• Remove products permanently.

—OR—

• Relocate air inlet and vent

terminations to other areas.

Removing from existing vent

Follow the instructions in Section 1, page 10 of this manual
when removing a boiler from an existing vent system.

Vent and air piping

Vent and air system:

Installation must comply with local
requirements and with the National Fuel
Gas Code, NFPA 54 / ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.

You must also install air piping from outside to the boiler
air intake adapter. The resultant installation is direct vent
(sealed combustion).

You may use any of the vent/air piping methods covered in
this manual. Do not attempt to install the Crest using any
other means.

NOTICE

ƽ WARNING

ƽ WARNING

ƽ WARNING

When determining equivalent combustion air and vent
length, add 5 feet (1.5m) for each 90° elbow and 3 feet (.9 m)
for each 45° elbow.

EXAMPLE: 20 feet (6 m) of pipe + (4) 90° elbows + (3) 45°
elbows = 49 equivalent feet (15 m) of piping.

Model

AIR INLET

VENT

Input

De-Rate per

25 feet of Vent

Air Intake

Diameter

Air Intake

Min. Length

Air Intake

Max. Length

Vent

Diameter

Vent

Min. Length

Vent

Max. Length

FB 1500

7"

12'

100'

7"

12'

100'

2%

FB 2000

8"

12'

100'

8"

12'

100'

2%

FB 2500

8"

12'

100'

9"

12'

100'

2%

FB 3000

10"

12'

100'

10"

12'

100'

2%

FB 3500

10"

12'

100'

10"

12'

100'

2%

Table 2B Direct Vent Minimum / Maximum Allowable Air / Vent Lengths

Model

Vent

Diameter

Vent

Min. Length

Vent

Max. Length

Input De-Rate per

25 feet of Vent

FB 1500

7"

12'

100'

1%

FB 2000

8"

12'

100'

1%

FB 2500

9"

12'

100'

1%

FB 3000

10"

12'

100'

1%

FB 3500

10"

12'

100'

1%

Table 2C Room Air Minimum / Maximum Allowable Air / Vent Lengths

2

General

venting

(continued)

DO NOT mix components from different
systems. The vent system could fail,
causing leakage of flue products into the
living space. Use only approved stainless
steel pipe and fittings.

Advertising