Vertical direct venting, Vent/air termination – vertical – Crestron electronic Crest Condensing Boiler 3.5 User Manual

Page 19

Advertising
background image

Installation & Operation Manual

19

3

Vertical direct venting

Vent/air termination – vertical

Prepare roof penetrations

1. Air

pipe

penetration:

a. Cut a hole for the air pipe. Size the air pipe hole as

close as desired to the air pipe outside diameter.

2. Vent pipe penetration:

a. Cut a hole for the vent pipe. For either combustible

or noncombustible construction, size the vent pipe

hole per the vent manufacturer’s instructions.

b. Insert a galvanized metal thimble in the vent pipe

hole (when required by local codes).

3. Space the air and vent holes to provide the minimum

spacing shown in FIG. 3-1.

4. Follow all local codes for isolation of vent pipe when

passing through floors, ceilings, and roofs.

5. Provide flashing and sealing boots sized for the vent pipe

and air pipe.

Termination and fittings

1. Prepare the vent termination coupling and the air

termination elbow (FIG. 3-1) by inserting bird screens.
Bird screens should be obtained locally.

2. The air piping must terminate in a down-turned 180°

return bend as shown in FIG. 3-1. Locate the air inlet
pipe no further than 2 feet (.6 m) from the center of the
vent pipe. This placement avoids recirculation of flue
products into the combustion air stream.

5. Locate terminations so they are not likely to be damaged

by foreign objects, such as stones or balls, or subject to
buildup of leaves or sediment.

ƽ WARNING

12" [305 MM] MINIMUM
ABOVE ROOF /
SNOW LINE

VENT OUTLET
36" [914 MM] MINIMUM
ABOVE AIR INLET

BIRD SCREEN
[TYPICAL]

Figure 3-2 Vertical Termination of Air and Vent w/Rain
Cap

Follow instructions below when determining
vent location to avoid possibility of severe
personal injury, death or substantial property
damage.

Installation must comply with local
requirements and with the National Fuel
Gas Code, NFPA 54 / ANSI Z223.1 - latest
edition for U.S. installations or CSA B149.1
Installation Code for Canadian installations.

ƽ WARNING

NOTICE

ƽ WARNING

Do not connect any other appliance to the
vent pipe or multiple boilers to a common
vent pipe except as noted in Section 2 on
page 18. Failure to comply could result in
severe personal injury, death, or substantial
property damage.

Determine location

Locate the vent/air terminations using the following guidelines:

1. The total length of piping for vent or air must not exceed

the limits given in the General Venting Section on page 17
of this manual.

2. The vent must terminate at least 3 feet above the highest

place in which the vent penetrates the roof and at least 2 feet
above any part of a building within 10 horizontal feet.

3. The air piping must terminate in a down-turned 180°

return pipe no further than 2 feet (.6 m) from the center of
the vent pipe. This placement avoids recirculation of flue
products into the combustion air stream.

4. The vent piping must terminate in an up-turned coupling

as shown in FIG. 3-1. The top of the coupling or the rain
cap must be at least 36" (914 mm) above the air intake. The
air inlet pipe and vent pipe can be located in any desired
position on the roof, but must always be no further than 2
feet (.6 m) apart and with the vent termination at least 36"
(914 mm) above the air intake.

Rooftop vent and air inlet terminations
must terminate in the same pressure zone,
unless vertical vent sidewall air is set up as
shown in the General Venting - Vertical
Vent, Sidewall Air Section.

BIRD SCREEN
[TYPICAL]

VENT OUTLET

36" MINIMUM

ABOVE AIR INLET

VENT

COMBUSTION AIR

12" [305 MM] MINIMUM
ABOVE ROOF /
SNOW LINE

Figure 3-1 Vertical Termination of Air and Vent

Advertising