General, Venting – Crestron electronic Crest Condensing Boiler 3.5 User Manual

Page 18

Advertising
background image

Installation & Operation Manual

18

2

General

venting

Common venting

Crest boilers may be common vented; however, the following
criteria MUST BE followed:

1. Only Crest boilers may be connected to the common

vent. DO NOT mix other manufacturer’s appliances or

other Lochinvar models.

2. Crest boilers connected to the common vent must all be

of the same size.

3. Each Crest boiler must have a Lochinvar supplied flue

damper installed (see Table 2D).

4. Only vertical venting may be used when common venting

Crest boilers. Sidewall venting is not allowed.

5. Crest boilers in a common vent must be connected and

controlled with the integral Crest SMART TOUCH

Cascade.

a. The Leader may be controlled through the Crest

SMART TOUCH control through BMS (external

0 - 10V signal), ModBus or its own internally

calculated

set

point.

b. The Cascade (Members) must be controlled by the

Crest Leader boiler using the efficiency optimized

Cascade.

For approved common vent sizing, contact the factory.

ƽ WARNING

When Crest boilers are common vented,
the criteria above MUST BE followed.
Failure to follow all these requirements
will result in severe personal injury, death,
or substantial property damage.

Table 2D Flue Damper Kits

Flue Damper Kits

Model

Damper Size

Kit Number

FB1500

7"

DRH30000

FB2000

8"

DRH30001

FB2500

9"

DRH30002

FB3000

10"

DRH30003

FB3500

10"

DRH30003