Diagrams, Installation & operation manual, Figure 12-1 ladder diagram – Crestron electronic Crest Condensing Boiler 3.5 User Manual

Page 58

Advertising
background image

58

Installation & Operation Manual

JUNCTION BOX

TERMINAL STRIP
120V SUPPLY "L"

TERMINAL STRIP
120V SUPPLY "N"

120VAC

NEUTRAL

INTEGRATED CONTROL

ON/OFF

SWITCH

F2

3.15 A

F4

5.0 A

SYSTEM PUMP

RELAY

BOILER PUMP

RELAY

DHW PUMP

RELAY

X1-1

X1-2

X1-4

X1-8

X2-4

SMALL BLOWER

RELAY

LARGE BLOWER

RELAY

SMALL GAS

VALVE RELAY

LARGE GAS

VALVE RELAY

X1-6

X10-1

X10-2

X10-3

SMALL GAS

VALVE RELAY

LARGE GAS

VALVE RELAY

X10-6

X10-5

X10-4

GAS

VALVE

(LARGE)

GAS

VALVE

(SMALL)

TERMINAL STRIP

SYSTEM PUMP

CONTACTOR

BOLIER PUMP

CONTACTOR

DHW PUMP

CONTACTOR

SMALL BLOWER

RELAY

LARGE BLOWER

RELAY

SMALL BLOWER

LARGE BLOWER

X6-10

X13-4

X6-1

X2-5

2

1

3

2

1

3

MODBUS

X1-1

X1-2

X1-3

FLUE DAMPER

TRANSFORMER

M

1

2

3

24V

TRANSFORMER

FLUE DAMPER

X6-3

X1-12

X1-3

LWCO

BOARD

TEST

SWITCH

LWCO

PROBE

LWCO RESET

J3-6

J3-3

J2-1

J2-2

J3-5

J3-2

J3-4

X6-5

X6-15

X6-12

X13-1

X6-6

X3-3

X3-4

X3-1

X3-2

X6-11

X6-2

X6-14

INTEGRATED

CONTROL

GPS1

GPS2

GPS3

BLOWER PROVING

SWITCH (LARGE)

BLOWER PROVING

SWITCH (SMALL)

BLOCKED FLUE

SWITCH

BLOCKED DRAIN

SWITCH

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

ALARM
CONTACTS

RUN-TIME
CONTACTS

TANK
THERMOSTAT

LOUVER
PROVING

24 VAC LOUVER
RELAY COIL

AUX
SWITCH 1

AUX
SWITCH 2

ENABLE

R

W

SMALL

CONNECTION BOARD

CN1-4

CN1-5

CN1-6

CN1-12

CN1-10

X6-13

X6-4

CN1-11

CN1-9

CN1-8

CN1-7

CN1-1

CN1-2

CN1-3

HIGH LIMIT

SWITCH

X1-3

X1-7

X1-10

X2-5

FLAME

SENSE 2

FLAME

SENSE 1

SPARK

GENERATOR

SPARK

ROD

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

SHIELD

SHIELD

A

B

MODBUS
OPTION

+

-

-

+

RATE
OUT

BOILER
PUMP OUT

SYSTEM RETURN
SENSOR

SYSTEM SUPPLY
SENSOR

0-10V

0-10V

TANK
SENSOR

OUTDOOR
SENSOR

+

+

-

-

0-10V

0-10V

BMS
IN

SYSTEM
PUMP IN

SHIELD

SHIELD

A

B

CASCADE

LARGE

CONNECTION BOARD

CN6-1

CN3-6

CN3-7

CN3-14

CN3-13

CN3-11

CN3-9

CN3-8

CN3-1

CN3-2

CN3-3

CN3-4

CN6-2

CN6-3

CN3-10

CN3-12

MODBUS

BOARD

X4-1

X4-2

X4-3

X6-3

X6-1

X6-2

X8-20

X8-10

X7-8

X8-13

X8-14

X8-12

INTEGRATED

CONTROL

CN3-4

X8-15

X7-7

X8-11

X8-6

X8-16

X8-7

X8-17

X8-1

-T

-T

-T

-T

-T

-T

-T

-T

-T

INLET SENSOR

OUTLET SENSOR (S9)

OUTLET SENSOR (S1)

FLUE SENSOR

FLUE SENSOR (S10)

PRE-MIX SENSOR 1 (S11)

PRE-MIX SENSOR 1 (S13)

PRE-MIX SENSOR 2 (S12)

PRE-MIX SENSOR 2 (S14)

X8-3

X8-8

X8-2

X8-4

X8-9

X7-1

X7-5

X7-2

X7-6

GROUND

X6-18

X6-9

X6-17

X6-8

X13-2

X13-3

1

2

4

5

1

2

4

5

SMALL BLOWER

LARGE BLOWER

1.5A EACH MAX

X11

CN3

CN1

DU941

LCD

DISPLAY

X4

RIBBON CABLE

X5-1

X5-7

X5-2

X5-8

X5-3

X5-9

X5-4

X5-10

X5-5

X5-41

X5-6

X5-12

BOX DEPICTS

OPTIONAL ITEMS

BOX DEPICTS

DUAL SENSOR

SINGLE HOUSING

HIGH VOLTAGE

LOW VOLTAGE
120 VAC

Notes:
1. All wiring must be installed in accordance with: local, state, provincial and national code requirements per either N.E.C. in USA or
C.S.A. in Canada.
2. If any original equipment wire as supplied with the appliance must be replaced, it must be replaced with wire having same wire gauge
(AWG) and rated for a minimum of 105°C. Exceptions : Replacement high voltage spark lead and ribbon cables must be purchased
from the factory. Use of a non-approved spark lead or ribbon cables can lead to operational problems which could result in
non-repairable damage to the integrated controller or other components.
3. Actual connector block locations may vary from those shown on diagrams. Refer to actual components for proper connector block
locations when using diagrams to troubleshoot unit.

LADDER DIAGRAM

LBL20281 REV A

USB

INTERFACE

"X5"

BLOCK WIRING

IS MODEL

DEPENDANT

X8-1

X8-5

12

Diagrams

Figure 12-1 Ladder Diagram