Maintenance

Maintenance and annual startup

Table 11A Service and Maintenance Schedules

Service technician

(see the following pages for instructions)

General:

• Address reported problems, if any

• Inspect interior; clean and vacuum if

necessary;

• Clean condensate trap and fill with fresh

water

Check for leaks (water, gas, flue,

condensate)

• Verify flue and air lines in good condition

and sealed tight

• Check system water pressure/system

piping/expansion

tank

• Check control settings

• Check the ignition and both flame sense

electrodes (sand off any deposits; clean

and

reposition)

• Check wiring and connections

Perform start-up checkout and

performance verification per Section 9.

• Flame inspection (stable, uniform)

• Check both flame signals (at least 10
microamps at high fire)

Clean the heat exchanger


• Test low water cutoff (reference the
Crest Service Manual).

If combustion or performance
indicate need:

• Clean heat exchanger


Remove and clean burner using

compressed air only

• Clean the blower wheels

ANNUAL START-UP

Owner maintenance

(see the Crest User’s Information Manual for

instructions)

Daily

• Check boiler area

Check pressure/temperature

gauge

Monthly

• Check vent piping

• Check air piping

• Check air and vent termination

screens


• Check relief valve

• Check condensate drain system

Every

6 months

• Test low water cutoff

• Reset button (low water

cutoff)

• Check boiler piping (gas and

water)

for

leaks

• Operate relief valve

End

of season

months



• Shut boiler down (unless boiler

used for domestic hot water)