28

Installation & Operation Manual

5

Hydronic piping

Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.

NOTICE

HOT WATER

GENERATOR

WATER

GENERATOR

CIRCULATOR

BOILER PUMP

(TYPICAL)

FLOW CHECK
VALVE (TYPICAL)

Y-STRAINER
(RECOMMENDED)

RELIEF

VALVE

BALL VALVE
(TYPICAL)

AIR SEPARATOR

DRAIN PORT
(TYPICAL)

SYSTEM
CIRCULATOR

BACK FLOW
PREVENTER

PRESSURE
REDUCING VALVE

PRESSURE
GAUGE

EXPANSION
TANK

FROM SYSTEM

TO SYSTEM

MAKE UP
WATER

BOILER DRAIN

(TYPICAL)

SYSTEM RETURN
SENSOR

SYSTEM SUPPLY
SENSOR

Figure 5-3 Multiple Boilers - Common Header - Recommended - Primary / Secondary Flow

Model

Number of Units

2

3

4

5

6

7

8

Recommended Common Header Pipe Sizes in Inches

FB 1500

4

4

5

5

6

6

7

FB 2000

4

5

5

6

7

7

8

FB 2500

5

5

6

7

7

8

10

FB 3000

5

6

7

7

8

10

10

FB 3500

5

6

7

8

10

10

10

NOTICE

A system supply sensor (factory supplied) MUST BE installed for proper boiler operation.

Table 5C Multiple Boilers - Common Header - Primary / Secondary Flow

System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in
operation to prevent short cycling and high limit issues.

NOTICE

[Based on a boiler ΔT of 30°F.]