Installation & Operation Manual

6

Gas connections

Connecting gas supply piping

1. Refer to FIG. 6-1 to pipe gas to the boiler.

a. Install ground joint union for servicing, when

required.

b. In Canada – When using manual main shutoff

valves, it must be identified by the installer.

Figure 6-1 Gas Supply Piping

2. Support piping with hangers, not by the boiler or its

accessories.

Do not check for gas leaks with an open
flame – use the bubble test. Failure to
use the bubble test or check for gas leaks
can cause severe personal injury, death, or
substantial property damage.

3. Purge all air from the gas supply piping.

4. Before placing the boiler in operation, check the boiler

and its gas connection for leaks.

a. The appliance must be disconnected from the gas

supply piping system during any pressure testing of

that system at a test pressure in excess of 1/2 PSIG

(3.5 kPa).

b. The appliance must be isolated from the gas supply

piping system by closing a manual shutoff valve

during any pressure testing of the gas supply piping

system at test pressures equal to or less than 1/2 PSIG

(3.5

kPa).

c. The appliance and its gas connection must be leak

tested before placing it in operation.

The gas valve and blower will not support
the weight of the piping. Do not attempt
to support the weight of the piping with
the boiler or its accessories. Failure to
comply could result in severe personal
injury, death, or substantial property
damage.

ƽ WARNING

ƽ WARNING

5. Use pipe sealing compound compatible with propane

gases. Apply sparingly only to male threads of the pipe
joints so that pipe dope does not block gas flow.

GAS SUPPLY

UNION
(FACTORY SUPPLIED)

MANUAL SHUTOFF

VALVE

(FACTORY SUPPLIED)

SEDIMENT TRAP /
DRIP LEG CLEAN OUT
(FACTORY SUPPLIED)

Failure to apply pipe sealing compound as
detailed in this manual can result in severe
personal injury, death, or substantial
property damage.

ƽ WARNING

Model

Gas Inlet Size

FB1500

1 1/2"

FB2000

1 1/2"

FB2500

2"

FB3000

2"

FB3500

2"

Table 6A Gas Inlet Size

For dual fuel models, reference the Crest
Dual Fuel Supplemental Manual.

NOTICE