Rice Lake SURVIVOR LaserLight Series Stop/Go Remote Displays - Installation & Operation Manual User Manual

Page 25

Advertising
background image

Configuration

21

3.7.2

Set or Get the Digital I/O (7 Segment with Stop/Go Light)

Version 2.05 only accepts the serial digital I/O commands listed in this manual. All previous serial digital I/O
commands prior to Version 2.05 will not work properly with this product.

The digital outputs are set to High (OFF) on reset.

Table 3-8. Serial Commands (Basic Configuration)

To use the two Digital Inputs and Digital Outputs, use J1 (See Figure 2-8 8) to connect and use the following
message command formats to set or get the Digital I/O

Set Relay (set relay output 1 off)

|00SR1OFF!

Response: OK = success (State: DO1_+5V) or ?? = error

Get Digital (input) 0

|00GRO!

Response: ON = gnd or OFF = +5V

Get Digital input levels (all digin)

|00DI!

Response: 0 = LL, 1 = LH 2 = HL, 3 = HH

Set Digital output levels to HH (all digout = +5V)

|00DO3!

Response: OK = success (states: DO0=DO1=+5V) or ?? = error

Traffic Light State

Dry Contact

Serial Commands

Stop

Dig0 and Dig1 open circuit

|00DO3!

Green Circle

Dig0 open circuit; Dig1 pulled low

|00DO2!

Green Arrow

Dig0 pulled low; Dig1 open circuit

|00DO1!

Off

Dig0 and Dig1 pulled low

|00DO0!