COnFIgurATIOn menu

The Steffes 2100 Series room heating units have a Configuration Menu which

allows the heaters to be customized to the power company and consumer’s

needs. This menu can be accessed on start-up and allows configuration settings

to be easily adjusted.
Accessing the Configuration Menu

Step 1 Energize the heater. Access to the Configuration Menu is allowed

for the first two (2) minutes of operation. If the heater has been

energized for over two (2) minutes, it must be powered off and

back on again.

Step 2 Press and release the M button until the faceplate displays “CONF”.
Step 3 Press the up arrow once and the faceplate will display “C000”. The display will flash between “C000”

and the corresponding configuration value.

Step 4 If necessary, edit the configuration by pressing and holding the M button while using the up or the down

arrow button to change the value.

Step 5 Once the value is correct, release the buttons and press the up arrow button to go to the next configuration

(C001, C002, etc.).

Step 6 Repeat steps 4 through 5 until all configuration settings have been adjusted to the desired values.
Step 7 Once configured, use the down arrow to leave the Configuration Menu.
In most applications only a few, if any, configuration changes will be necessary. Following is a description of the

configuration settings and their functions:
C000

Off-Peak Method of Charge Control - Sets the method of brick core charging to be used during off-peak

(charge) periods. Heater is configured for automatic charge control, which is a value of five (5). To utilize

manual charge control, change the value to six (6).

C001

Start Brick Core Charge Set Point - If utilizing automatic charge control as set in C000, this value

indicates the outdoor temperature at which the heater will start charging.

C002

Full Brick Core Charge Set Point - If utilizing automatic charge control as set in C000, this value

indicates the outdoor temperature at which the heater will target a full core charge.

C003

Power line Carrier (PlC) Channel Selection - If using PLC communication, this setting must match

the channel setting in the Steffes PLC transmitting device. A value of zero indicates power line carrier

communication is disabled.

C004

Optional Controls Configuration

Value

Configuration Description

154

No Time Clock Module/Utilizing PLC or Manual Charge Control

155

No Time Clock Module/Direct Wired Outdoor Sensor

158

Time Clock Module/Manual Charge Control

159

Time Clock Module/Direct Wired Outdoor Sensor

C005

Control Switch Configuration - If utilizing power line carrier control, the Steffes time clock module or

line voltage control, this value should be zero. For all other applications, this value should be one (1).

C006

This configuration MUST be set to a value of six (6) for all 2100 Series room heating units.

C007

Charge Factor - This configuration should be set to a value of thirty (30).

C008-C012 Currently not utilized in 2100 Series room heating units.
C013-C021 Time Clock Module Configuration - These configuration settings are used to configure the peak

control times when utilizing the optional Steffes Time Clock Module. Refer to the installation and

configuration instructions included with the module for more information.

208V SYSTEMS ONlY:

In standard configuration, Steffes heaters are dual rated for 240V and 208V power connections. The

heaters are factory configured for 240V. If the control circuit is operating on 208V power, the value in

location 16 (l016) must be changed to 210 and the value in location 28 (l028) must be changed to 5.

If access to Configuration

Menu times out, the system

must be powered off at the

circuit breaker and back on

to re-enter the menu.