The 2100 series room heating unit contains a Help Menu which may be accessed by pressing and releasing the M

button until "HELP" is displayed on the faceplate. Scroll through the menu by pressing either the up or the down

arrow button.

Display

reading Description

Fxxx

Firmware Version Number - Indicates the version of software installed.

O xx

Outdoor Temperature - Indicates current outdoor temperature as recognized by the heater.

tL:xx

Target Level - Indicates the percentage of brick core charge the heater targets during an off-peak

period.

CL:xx

Charge Level - Indicates the percentage of heat storage currently in the brick core.

HE x

Heating Elements Active - Indicates the number of heating elements currently energized.

PC x

Power Line Carrier Channel - Indicates the channel on which the heater is set to receive PLC

communication signal.

P x

Power Line Carrier Net Hit Rate Percentage - Indicates the percentage of "GOOD" communication

packets received by the heater from the PLC transmitter system.

PS x

Indicates which Specialty Timer the system is currently using. The value displayed will be zero if

the Specialty Timer is not being utilized.

CC_x

Charge Mode Operation - Indicates the charge control method being utilized during off-peak

periods.

CA_x

A-Peak Mode Operation - Indicates the charge control method being utilized during anticipated

peak periods.

C1_x

Specialty Timer #1 Charge Mode - Specialty Applications Only.

C2_x

Specialty Timer #2 Charge Mode - Specialty Applications Only.

HUxx

Heat Usage - Indicates the amount of input being dissipated by the system.

A_xx

Target Discharge Air Temperature - Indicates the discharge air temperature that the system is

targeting.

cxxx

Compressor Output Relay Delay Timer - Indicates time remaining before heat pump compressor is

energized. "c ON" indicates the heat pump is energized.

errOr CODeS

2100 Series heaters have an on-board diagnostic system to monitor various

operating conditions. If operating conditions move outside the normal

operating range, an error code will be displayed on the faceplate. If there are

multiple errors simultaneously, only the highest priority error code will be

displayed. Once corrected, the next highest priority code will be displayed.

Error codes will be displayed on the faceplate as “Er—” (i.e. Er05).

Error Code

Description

01

Core temperature sensor reading is out of normal range.

An open, shorted, or otherwise defective sensor or a circuit

board which is out of calibration could cause this.

02

Contact a qualified service technician.

HAZARDOUS VOLTAGE:

Risk of electric shock. Can

cause injury or death. Heater

may be connected to more

than one branch circuit.

Disconnect power to all

circuits before servicing.

DO NOT remove the painted

front panel while energized.

Equipment must be serviced

by a qualified technician.

WARNING