Caution, Brick core temperature sensor installation – Steffes 9180 User Manual

Page 16

Advertising
background image

Step 4 Lower insulation blankets back into position, one at a time. Carefully tuck the sides of the insulation into

the edges, corners, and around the exposed portions of the heating element to ensure maximum efficiency.

Use face mask, gloves, and long sleeved garments when handling insulation materials in ac-

cordance with generally accepted safety practices.

Step 5 Reinstall the galvanized front panel and secure it to the system using the screws originally removed.
Step 6 Route element harnesses through connectors, using one connector/harness until tape is centered.
Step 7 Attach element lead wires to element terminals. Start at the top using the appropriate color chart below.

Repeat pattern as necessary. The neutral white wires are jumpered together in sets of three.

277/347V = Black (Top)

208/240V = Black (Top)

240V = Black (Top)

Systems

White

3phase

Red

1phase

Red

Red

Systems

Blue

Systems Black

White

Black

Red

Blue

Red

White

Blue

Step 8 Route the orange wire to the electrical compartment. Cut the wire and crimp ends (found on orange/

black wires in electrical compartment). Connect the orange wires to the orange/black wires.

Step 9 Remove the blower access cover from the base left side. Locate the blue core blower wires and purple

(violet) water temperature sensor wires.

Step 11 Route the wires through the flanged hole at the front left corner of the base. Continue routing up to the

electrical compartment through 1/2" knockout. Connect the blue core blower wires to black and the blue

wires. Connect the two purple (violet) wires to the two purple wires..

Step 1 Remove the screw(s) by the brick core temperature sensor con-

nector holes in the galvanized front panel.

Step 2 Route the brick core sensors through the 1/2" knockout up to

the relay driver board. The yellow wire from each sensor must

be connected to the Y terminal of the proper sensor connection

terminal block, and red to R. Polarity of sensors is critical.

Sensor connections MUST be installed as follows:

Single Module - 9150 or 9180 (Figure 7)

Bottom sensor to core C

Second sensor to core D

Third (if equipped) to core E

Step 3 Insert the brick core temperature sensors through the holes in

the galvanized front panel. The sensors must pass through the

blanket and board insulation and into the brick core. Use the

sensors to aid in making a passageway by rotating the sensors

while gently pushing inward.

Step 4 Once brick core sensors are installed, re-install sensor mount-

ing screws to secure and ground the sensors.

Risk of improper operation. Proper installation of the brick core temperature sensor is critical to

the operation of the heating system. Read and follow installation instructions carefully.

CAUTION

CORE TEMPERaTURE SENSOR

CONNECTIONS

FIgURE 7

Core

Temperature

Sensors

Connect To Core "E"

On 80kW Module Only

Relay

Driver

Board

Connect To

Core "D"

Connect To

Core "C"

installa

tion

installa

tion

T

herm

e

lecT

h

ydronic

i

nSTallaTion

3.07

i

nSTallaTion

3.06

T

herm

e

lecT

h

ydronic

Brick core teMPerature SenSor inStallation