MOdEL 9180 (80kW Storage Module)

* Supply via stepdown transformer - field installed.

** Add approximately 500 lbs to arrive at shipping weight.

a

ppendix

a

ppendix

T

herm

e

lecT

h

ydronic

a

ppendix

A.02

a

ppendix

A.01

T

herm

e

lecT

h

ydronic

Input Voltage

240

120/208

120/240

277/480

347/600

Phase

1

3

3

3

3

Number of Wires

2

3

3

4

4

Charging Input

(kW)

80.0

72.0

80.0

75.6

80.0

Elements - Quantity

Elements - Watts Each

18

4,444

18

4,000

18

4,444

18

4,200

18

4,444

Amps – Core Charging

333.30

200.09

192.66

90.97

76.84

Maximum Pump & Blower Load

(AMPS)

4.6

4.6

4.6

2.3

1.9

Minimum Circuit Ampacity

422.38

255.86

246.57

116.59

98.43

Minimum Fuse Size

450

300

250

125

100

Maximum Fuse Size

450

300

300

150

125

Blowers/System Control Voltage*

240V/208V

Storage Capacity - kWh

Storage Capacity - BTU

480

1,637,760

Pipe Size

(Inlet/Outlet)

1 ½”

Required Primary Loop

Minimum of 12’ of 1 ½” pipe required in primary loop plumbing

Output Water Temperature

(selection range)

50

o

F to 185

o

F

Maximum Working Pressure

20 PSIG requires 30 PSI Pressure Relief Valve

60 PSIG requires 75 PSI Pressure Relief Valve (Standard)

125 PSIG requires 150 PSI Pressure Relief Valve

Minimum Flow Rate

(Primary Loop)

1 GPM per 10,000 BTU of required output at 20

o

F Temperature

Rise (30 GPM maximum)

Internal Pressure Drop

(assuming 50% glycol mix)

.7 ft @ 15 GPM

1.8 ft @ 25 GPM

1.2 ft @ 20 GPM

2.5 ft @ 30 GPM

Maximum Static Dissipation (Watts)

4,500

Approximate Heater Module Weight

(lbs)

970

Approximate Insulation Block / Elements /

Other Weight

(lbs)

400

Approximate Brick Weight

(lbs)

5,160

Number of Brick

288

Approximate Installed Weight

(lbs) **

6,530