MOdEL 9150 (53kW Storage Module)

* Supply via stepdown transformer - field installed.

** Add approximately 500 lbs to arrive at shipping weight.

a

ppendix

a

ppendix

T

herm

e

lecT

h

ydronic

a

ppendix

A.02

a

ppendix

A.01

T

herm

e

lecT

h

ydronic

Input Voltage

240

120/208

120/240

277/480

347/600

Phase

1

3

3

3

3

Number of Wires

2

3

3

4

4

Charging Input

(kW)

53.3

48.0

53.3

50.4

53.3

Elements - Quantity

Elements - Watts Each

12

4,444

12

4,000

12

4,444

12

4,200

12

4,444

Amps – Core Charging

222.20

133.39

128.44

60.65

51.23

Maximum Pump & Blower Load

(AMPS)

4.6

4.6

4.6

2.3

1.9

Minimum Circuit Ampacity

283.50

172.49

166.30

78.69

66.41

Minimum Fuse Size

300

175

175

80

70

Maximum Fuse Size

300

200

200

100

100

Blowers/System Control Voltage*

240V/208V

Storage Capacity – kWh

Storage Capacity - BTU

320

1,091,840

Pipe Size

(Inlet/Outlet)

1 ½”

Required Primary Loop

Minimum of 12’ of 1 ½” pipe required in primary loop plumbing

Output Water Temperature

(selection range)

50

o

F to 185

o

F

Maximum Working Pressure

20 PSIG requires 30 PSI Pressure Relief Valve

60 PSIG requires 75 PSI Pressure Relief Valve (Standard)

125 PSIG requires 150 PSI Pressure Relief Valve

Minimum Flow Rate

(Primary Loop)

1 GPM per 10,000 BTU of required output at 20

o

F Temperature

Rise (30 GPM maximum)

Internal Pressure Drop

(assuming 50% glycol mix)

.7 ft @ 15 GPM

1.8 ft @ 25 GPM

1.2 ft @ 20 GPM

2.5 ft @ 30 GPM

Maximum Static Dissipation (Watts)

3,000

Approximate Heater Module Weight

(lbs)

900

Approximate Insulation Block / Elements /

Other Weight

(lbs)

330

Approximate Brick Weight

(lbs)

3,440

Number of Brick

192

Approximate Installed Weight

(lbs) **

4,670

Advertising