Step 1 Remove the exchanger access

panel and locate the pressure

relief valve assembly.

Step 2 Connect the pressure relief valve

to the outlet water port on the

left side of the ThermElect Hy-

dronic. It is extremely important

that the following conditions for installation of this part are met:

Insure all connections, including the valve inlet are clean and free from any foreign material.

Use pipe compound sparingly, or tape on external threads only.

Mount the pressure relief valve in a vertical, upright, position directly to the outlet water port of

the system. Under no circumstances should there be a flow restriction or valve of any type be-

tween the safety relief valve and the pressure vessel.

Step 3 Use schedule 40 pipe to install a discharge line for the pressure relief valve.

This discharge line MUST:

be connected from the valve outlet with no intervening valve and directed downward to a safe

point of discharge.

allow complete drainage of both the valve and the discharge line.

be independently supported and

securely anchored to avoid applied

stress on the valve.

be as short and straight as possible.

terminate freely to atmosphere

where any discharge is clearly vis-

ible and is at no risk of freezing.

terminate with a plain end that is

not threaded.

be constructed of a material suit-

able for exposure to temperatures

of 375

o

F or greater.

be, over its entire length, of a pipe

size equal to or greater than that of

the valve outlet.

air conDitioner/Heat PuMP interface

The ThermElect Hydronic system can be used in conjunction with an air conditioner or a heat pump. Contact

Steffes Corporation for more information.

PreSSure relief valve inStallation

available Pressure

Relief Valves

Minimum

BTU Rating

Maximum

Operating Pressure

Order

Item #

30 PSI

400,000

20 PSI

1100104

75 PSI

500,000

60 PSI

1100105

150 PSI

500,000

125 PSI

1100106

note: 9100 Series Systems are shipped with 75 pSi pressure relief valves.

if a different valve is required order the item number listed above.

WARNING

Risk of explosion. Can cause injury or death. The factory supplied pressure relief valve MUST be

connected to the system with the supplied fittings.

DO NOT modify this assembly.

DO NOT cap, plug, or otherwise obstruct the outlet of the pressure

relief valve.

DO mount the pressure relief valve in a vertical, upright position.

This pressure relief valve is sized to service the needs of the

ThermElect Hydronic heating system. If multiple heating systems

are being used, pressure relief valving for the other system MUST be

provided separately.

Risk of injury or property damage. During opera-

tion, the pressure relief valve may discharge large

amounts of steam and/or hot water. To reduce the

potential for bodily injury or property damage, install

a discharge line.

DO use schedule 40 pipe for the discharge line.

DO NOT use schedule 80, extra strong pipe or

connections on the discharge line.

DO NOT cap, plug, or otherwise obstruct the

discharge pipe outlet.

DO follow all local, state, and national codes

and regulations.

CAUTION