Steffes 9180 User Manual

Page 18

Advertising
background image

loW voltaGe electrical connectionS - outDoor

teMPerature SenSor (oPtional)

If using BaCNet control, the outdoor temperature sensor may not be used. Follow the in-

structions included with the BaCNet Controller.

If connecting to the Steffes power line carrier (PLC) system, follow the installation instruc-

tions in the PLC system's Owner's and Installer's guide.

Outdoor sensor wire MUST NEVER be combined with other control wiring in a multi-con-

ductor cable.

Theory of Operation: The outdoor sensor monitors outdoor temperature and provides this information to the

system. The system responds by automatically storing heat in its brick core according to

outdoor temperature and the heating requirements.

Location of: The outdoor sensor must be placed in a location where it can accurately sense outdoor temperature

and is not affected by direct sunlight or other abnormal temperature conditions.

Installation Methods: A) Hard wired to Steffes heating system "OS" and "SC" terminals (default)

OR

B) Connected to Power Line Carrier (PLC)

Wiring: • Route low voltage wire from the outdoor sensor to the electrical compartment through one of the

low voltage wire knockouts.

• Connect to "OS" and "SC" as shown in Figure 10.

• If the sensor wiring is routed through an external wall, the opening through which the wire is routed

MUST be sealed. Failure to do so may affect the accuracy of the outdoor temperature sensor.

• The outdoor sensor is supplied with a lead length of 40 ft. If a greater wire length is needed, it can

be extended to a total of 250 ft.

• No other loads can be controlled or supplied through this cable. It is for connection of the outdoor

sensor ONLY.

• This low voltage cable MUST not enter any line voltage enclosure.

• Unshielded Class II (thermostat) wire can be used as extension wire provided it is segregated from

any line voltage cabling.

loW voltaGe electrical connectionS - rooM

tHerMoStat (oPtional)

A low voltage (24VAC) room thermostat can be used for room temperature control with the ThermElect Hydron-

ic system. If so, Steffes recommends using a digital thermostat. To iniate a heat call, the system needs a switch

closure from R to H. This energizes the primary loop pump outputs.

12-Position Low Voltage Terminal Block Coding
R = Low Voltage Hot

C = Low Voltage Common

Y = Compressor/Stage 1 Heat Call

W = Stage 2 Heat Call

Y2 = Compressor Output

G = Fan Call

O = Reversing Valve Input

O2 = Reversing Valve Output

H = Hydronic Heat

OS = Outdoor Temperature Sensor

SC = Temperature Sensor Common

DS = Duct Temperature Sensor

installa

tion

installa

tion

T

herm

e

lecT

h

ydronic

i

nSTallaTion

3.09

i

nSTallaTion

3.08

T

herm

e

lecT

h

ydronic

LOW VOLTagE CONNECTIONS

HydRONIC HEaTINg SINgLE ZONE SySTEM

FIgURE 10

Outdoor Sensor

Hydronic Heat Thermostat, Zone

Valve, End Switch, or Pump Control

SC

H OS

W

O2

O

G

Y Y2

C

R

12 Position Terminal Block

DS