FREEZE PROTECTION: Risk of property damage. Hydronic

heating system freeze-ups WILL cause extensive damage to

the entire heating system and/or property. It is the responsi-

bility of the installer to provide protection against freezing.
PIPING SUPPORT: Risk of equipment damage or personal

injury. DO NOT use the exchanger as support for piping.

Support brackets should be in place to ensure proper op-

eration of the system and to keep pressure off the inlet and

outlet piping.

CAUTION

Heat Exchanger Flow and Restriction Properties

gPM

Velocity (Feet/Sec)

Restriction 150° Water

(Feet of Heatd)

Restriction 80°

50% Propylene glycol

(Feet of Head)

5

0.6

0.1

0.2

10

1.2

0.3

0.6

15

1.8

0.7

1.3

20

2.4

1.2

2.1

24.5

3

1.7

3.1

25

3.1

1.7

3.2

30

3.7

2.4

4.5

Capacity

3.4 Gallons

Maximum Flow

30 GPM

Tubing Material

Copper

Maximum Outlet

Water Set Temperature

180°F

HEAT EXCHANGER SPECIFICATION

2" MINIMUM

HEATING

VALVE

CHECK

UP15-42F

LOOP

PRIMARY

PUMP

ZONES

TO

2" MINIMUM

BALANCING

VALVE

FROM

HEATING

ZONES

9180

9180

9150

9150

MULTIPLE UNITS SySTEM PLUMBINg WITH MaSTER LOOP

FIgURE 13

NOTES:

1. Check valves on the return side are recommended to

prevent back flow into the furnace.

2. Balancing valves are recommended to provide an even

flow of water between all units.

3. Flow must continue for a minimum of 30 seconds after

call for heat ends.