Kistler-Morse KM Microcell Bolt-On User Manual

Page 17

Advertising
background image

Note

TB3 terminal block has 12 terminals to
accommodate up to four Microcells™ (A, B,
C, and D). Locate the terminal labeled for the
Microcell™ you are wiring.

5. Estimate the required length of cable to the

terminal strip, allowing a little extra for strain

relief. Cut the excess cable.

6. Strip back 3 in (76mm) of the cable sheathing

to expose the three wires inside. Strip back

¼” (6mm) of insulation from the end of each of

the wires.

7. Connect the wires from the Microcell™ to the

selected TB3 terminals; black wire to B

terminal, white wire to W terminal, and red wire

to R terminal.

8. Perform Steps 2 through 7 for each Microcell™

you wire to this junction box (up to four).

9. Spread a generous bead of sealant (Sikaflex

1A polyurethane sealant or Dow Corning RTV

738 or RTV 739) around the sides of the plug

for each hole not being used. Screw a plug

into each hole.

10. Replace the junction box cover and screws

if not ready to begin wiring the junction boxes

together to ensure that no moisture enters the

junction box.

WIRING JUNCTION BOXES
TOGETHER AND TO
SIGNAL PROCESSOR

There are two versions of the junction box
enclosure. Both versions have four small holes
for wiring Microcells™ to the junction box, as
described previously. In addition, the junction box
has one or two large holes:

1. One large hole for conduited installation. The

large hole, which accommodates a ¾” conduit

fitting, is for wiring the junction box to the other

junction boxes and to the signal processor.

2. Two large holes for non-conduited

installation. The two large holes, which are

equipped with PG13.5 cable fittings, are for

wiring the junction box to the other junction

boxes and to the signal processor.

Kistler-Morse

®

requires the use of cable

trays for non-conduited installations.

Note

A. The following procedure assumes the

conduit/cable tray has been installed.

B. Seal all conduit fittings against water

entry. Install drain holes at the conduit’s

lowest elevation(s) to allow condensation

to drain.

C. Use Belden™ 3-conductor shielded

interconnect cable or equivalent to wire

junction boxes together and to the signal

processor. For lengths up to 1,000 ft

(305m), use 18 gauge Belden™ 8791 cable.

For lengths from 1,000 ft to 2,000 ft (305m

to 610m), use 16 gauge Belden™ 8618

cable.

D. When wiring cable to junction box

terminals, strip back 3 in (76mm) of cable

sheathing to expose the 3-conductor wires

and shield wire inside. Strip ¼” (6mm) of

insulation from the end of each of the

conductor wires.

E. All wiring routed between the junction

boxes and signal processor must be

continuous with no splices.

CAUTION

Only use Sikaflex 1A polyurethane sealant or
Dow Corning RTV 738 or RTV 739.
Other
sealants may contain acetic acid, which is
harmful to sensors and electronics.

1. Remove the junction box cover.

For a conduited installation, install a conduit

fitting in the large hole in the bottom of the

junction box.

For a non-conduited installation, See Figure

3-14. Spread a generous bead of sealant

around the sides of the PG13.5 cable fittings.

Install the fittings in the two large holes in the

bottom of the junction box.

Figure 3-14. Inserting Shielded Interconnect

Cable Through PG13.5 Fitting and Cap.

13

Advertising