Mounting junction box – Kistler-Morse KM Microcell Bolt-On User Manual

Page 26

Advertising
background image

8. To complete installation, ensure that both

screws are tightened until the T-handle driver

flexes in torsion, ¼ turn past the point where

the screw stops turning, with this flexing

procedure repeated several times to ensure the

screw is tight, and the voltage is in the range

-100mV to +100mV.

9. Repeat Steps 2 through 8 to install

Microcell™ B on the other side fo the web.

10. Prior to installing the environmental cover,

ensure the mating surface on the web is free

of dirt and grease. Reclean if necessary, being

careful not to remove the rust inhibitor on the

bare metal.

11. See Figure 4-8. Apply a generous bead of

sealant to the inside flange of the

environmental cover. Add extra sealant to the

cable exit channel.

A. Align the environmental cover over the

installed Microcell™ A, with the cable

through the cover’s exit channel.

B. Press the cover against the web, squeezing

out the sealant around the edges. Be

careful not to squeeze too much sealant

out.

C. Use your finger to smooth the sealant

around all edges and joints, eliminating

areas where moisture may pool, especially

along the top edge. Verify the sealant

forms a continuous, watertight seal. Ensure

the cable exit channel is completely sealed.

D. Repeat Step 11 for Microcell™ B.

CAUTION

Only use Sikaflex 1A polyurethane sealant or
Dow Corning RTV 738 or RTV 739
. Other
sealants may contain acetic acid, which is
harmful to sensors and electronics.

Figure 4-8. Environmental Cover.

12.If you created any holes that go completely

through the web, spread sealant (Sikaflex 1A

polyrethane sealant or Dow Corning RTV738

or RTV 739) over the open holes. Use your

finger to press sealant into each hole.

MOUNTING JUNCTION BOX

MOUNTING LOCATION

Each junction box can be wired to a maximum of
two Microcell™ sets (four Microcells™ total):
1. One set of Microcells™ on a beam; both

Microcells™ are wired to one junction box.

2. Two sets of Microcells™ on a beam; all four

Microcells™ are wired to one junction box if

the sets are sufficiently close to each other to

allow the Microcell™ cables to reach the

junction box.

See Figures 4-9 and 4-19. Locate the junction
box on the instrumented beam or on the
supporting column or horizontal beam. Ensure
you have sufficient cable length and that a drip
loop will be formed by the Microcell™ cables when
wired to the junction box.

Figure 4-9. Junction Box Location - Two

Microcells™ Per Junction Box.

Figure 4-9. Junction Box Location - Four

Microcells™ Per Junction Box.

JUNCTION BOX INSTALLATION

CAUTION

Do not install junction boxes in the rain.
Moisture in the junction box will cause
corrosion and system errors.

22

Advertising