APPENDIX A: MENU ITEM DESCRIPTIONS

Page 104 of 160 PR2: 04/22/13

Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Table A-1: Boiler Menu Item Descriptions

MENU LEVEL & OPTION

DESCRIPTION

SETUP MENU

Password

Allows password to be entered.

Once the valid password (159) is entered, options in
the Setup, Configuration and Tuning Menus can be
modified.

Language

Permits selection of English, Spanish or French for
displayed messages. Default is English.

Time

Displays time from 12:00 am to 11:59 pm.

Date

Displays dates from 01/01/00 to 12/31/99

Unit of Temp

Permits selection of temperature displays in degrees
Fahrenheit (°F) or degrees Celsius (°C). Default is
°F.

Comm Address

For RS-485 communications (0 to 127). Default
address is 0. RS-232 should have its own
(programmable) password.

Baud Rate

Allows communications Baud Rate to be set (2400
to 19.2K). Default is 9600.

Software Version

Identifies the current software version of the control
box (Ver 0.0 to Ver 9.9).

CONFIGURATION MENU

Internal Setpoint

Allows internal setpoint to be set. Default is 130°F.

Unit Type

Allows selection of KC Boiler, KC Boiler LN, BMK
Boiler Std, BMK Blr Std Dual, BMK Boiler LN, BMK
Blr LN Dual, KC Water Heater, KC Wtr Heater LN,
Innovation WH

Unit Size

Sets unit size from 600 MBH to 3000 MBH
depending on the Unit Type.

Fuel Type

Allows selection of Natural Gas or Propane. Default
is Natural Gas.

Boiler Mode

It allows selection of: Constant Setpoint, Remote
Setpoint, Direct Drive, Combination, or Outdoor
Reset Mode. Default is Constant Setpoint Mode.

Remote Signal

Used to set the type of external signal which will be
used when operating in the Remote Setpoint, Direct
Drive or Combination Mode. The factory default is
4-20 mA/1-5V.

Bldg Ref Temp

Allows the building reference temperature to be set
when operating a boiler in the Outdoor Reset Mode.
Default is 70°F.