APPENDIX E: BOILER DEFAULT SETTINGS

Page 120 of 160 PR2: 04/22/13

Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Table E-1: Boiler Default Settings (Continued)

MENU & OPTION

FACTORY DEFAULT

Configuration Menu --Continued

Network Timeout

30 seconds

Hi DB Setpt En

30

Demand Offset

10

Deadband High

2

Deadband Low

2

Tuning Menu

Prop Band

70°F

Integral Gain

1.00

Derivative Time

0.0 min