CHAPTER 7: MAINTENANCE

PR2: 04/22/13 Page 79 of 160


Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

13. Disconnect the inlet air flex hose from the air/fuel valve by loosening the hose clamp.

14. Remove the six (6) 1/4-20 hex nuts and flat washers securing the blower to the burner

plate (Figure 7-6).

15. Remove the blower and air/fuel valve from the burner plate by lifting straight up. Also,

remove the blower gasket, which will be replaced with a new gasket.

16. Remove the eight (8) 3/8-16 nuts from the burner flange (Figure 7-5) using a 9/16” wrench.

BLOWER

PROOF

SWITCH

BLOCKED

INLET

SWITCH

AIR/FUEL

VAVLE

STAGED

IGNITION

ASSEMBLY

FLAME
DETECTOR

BURNER

PLATE

HEX NUTS &

WASHERS (6)

BLOWER

GASKET

IGNITOR-

INJECTOR

BURNER

BLOWER

BURNER

GASKET

BURNER

GASKET

Figure 7-6: Burner Assembly Exploded View

NOTE

The burner assembly is heavy, weighing approximately
30 pounds.

17. Remove the burner assembly from burner flange by pulling straight up.

18. Remove and replace the two (2) burner gaskets.

NOTE

During reassembly, apply high-temperature, anti-seize
lubricant to the threads of the igniter-injector and
grounding screw. Also, ensure that the igniter-injector is
properly positioned as indicated in Figure 7-3. Torque the
igniter-injector to 15 ft-lbs.