CHAPTER 8: TROUBLESHOOTING GUIDE

Page 88 of 160 PR2: 04/22/13

Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

TABLE 8-1. BOILER TROUBLESHOOTING (Continued)

FAULT

INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

HIGH WATER

TEMP

SWITCH OPEN

1. Faulty Water temperature switch.

2. Incorrect PID settings.


3. Faulty shell temperature sensor.


4. Unit in Manual mode.

5. Unit setpoint is greater than Over Temperature

Switch setpoint.

6. Boiler Management System/AERCO Control

System PID or other settings not correctly
setup.

7. No interlock to boiler or BMS/ACS to disable

boiler(s) in event that system pumps have
failed.

8. System flow rate changes are occurring faster

than boilers can respond.

1. Test the temperature switch to insure it trips at its actual water

temperature setting.

2. Check PID settings against Menu Default settings in the Appendix.

If the settings have been changed, record the current readings then
reset them to the default values.

3. Using the resistance charts in the Appendix C, Measure the

resistance of Shell sensor and BTU sensor at a known water
temperature.

4. If unit is in Manual Mode switch to Auto Mode.

5. Check setpoint of unit and setpoint of Temperature Switch; Ensure

that the temperature switch is set higher than the unit’s setpoint.

6. Check the BMS/ACS for changes to PID default values, correct as

necessary.

7. If system pump is controlled by Energy Management System other

than BMS/ACS or pumps are individually controlled by boiler,
check to see if there are flow switches interlocked to the BMS/ACS
or boiler.

8. If the system is a variable flow system, monitor system flow

changes to ensure that the rate of flow change is not faster than
what the boilers can respond to.

HIGH WATER

TEMPERATURE

1. See HIGH WATER TEMPERATURE SWITCH

OPEN.

2. Temp HI Limit setting is too low.

1. See HIGH WATER TEMPERATURE SWITCH OPEN.

2. Check Temp HI Limit setting.

IGN BOARD

COMM FAULT

1. Communication fault has occurred between

the PMC board and Ignition/Stepper (IGST)
board

1. Press CLEAR button and restart unit. If fault persists, contact

qualified Service Personnel.