APPENDIX B: STARTUP, STATUS AND FAULT MESSAGES

Page 110 of 160 PR2: 04/22/13

Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Table B-2: Fault Messages

FAULT MESSAGE

FAULT DESCRIPTION

AIRFLOW FAULT
DURING PURGE

The Blower Proof Switch opened during purge,
or air inlet is blocked.

AIRFLOW FAULT
DURING IGN

The Blower Proof Switch opened during ignition.

AIRFLOW FAULT
DURING RUN

The Blower Proof Switch opened during run.

DELAYED
INTERLOCK OPEN

The Delayed Interlock is open.

DIRECT DRIVE
SIGNAL FAULT

The direct drive signal is not present or is out of range.

FFWD TEMP
SENSOR FAULT

The temperature measured by the Feed Forward (FFWD)
Sensor is out of range.

FLAME LOSS
DURING IGN

The Flame signal was not seen during ignition or lost within 5
seconds after ignition.

FLAME LOSS
DURING RUN

The Flame signal was lost during run.

HEAT DEMAND
FAILURE

The Heat Demand Relays on the Ignition board failed to
activate when commanded.

HIGH EXHAUST
TEMPERATURE

The High Exhaust Temperature Limit Switch is closed.

HIGH GAS
PRESSURE

The High Gas Pressure Limit Switch is open.

HIGH WATER
TEMPERATURE

The temperature measured by the Outlet Sensor exceeded
the Temp Hi Limit setting.

HIGH WATER TEMP
SWITCH OPEN

The High Water Temperature Limit Switch is open.

IGN BOARD
COMM FAULT

A communication fault has occurred between the PMC board
and Ignition board.

IGN SWTCH CLOSED
DURING PURGE

The Ignition Position Limit switch on the Air/Fuel Valve closed
during purge.

IGN SWTCH OPEN
DURING IGNITION

The Ignition Position Limit switch on the Air/Fuel Valve
opened during ignition.

INTERLOCK
OPEN

The Remote Interlock is open.

LINE VOLTAGE
OUT OF PHASE

The Line (Hot) and Neutral wires are reversed.

LOW GAS
PRESSURE

The Low Gas Pressure Limit Switch is open.

LOW WATER
LEVEL

The Low Water Cutoff board is indicating low water level.

NETWORK COMM
FAULT

The RS-485 network information is not present or is
corrupted.