CHAPTER 3: CONTROL PANEL OPERATION

PR2: 04/22/13 Page 37 of 160


Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

1. The DEMAND LED status indicator will light.

2. The unit checks to ensure that the Proof of Closure (POC) switch in the downstream

Safety Shut-Off Valve (SSOV) is closed. Figure 3-3 shows the Natural Gas SSOV
location for a Factory Mutual (FM) Gas Train.

3. With all required safety device switches closed, a purge cycle will be initiated and the

following events will occur:

a) The Blower relay energizes and turns on blower.

b) The Air/Fuel Valve rotates to the full-open purge position and closes purge position

switch. The dial on the Air/Fuel Valve (Figure 3-4) will read 100 to indicate that it is
full-open (100%).

Figure 3-3: SSOV Locations

4. Next, the blower proof switch on the Air/Fuel Valve (Figure 3-5) closes. The display

will show Purging and indicate the elapsed time of the purge cycle in seconds.

5. Upon completion of the purge cycle, the Control Box initiates an ignition cycle and the

following events occur:

a) The Air/Fuel Valve rotates to the low-fire ignition position and closes the ignition

switch. The dial on the Air/Fuel Valve (Figure 3-6) will read between 25 and 35 to
indicate that the valve is in the low-fire position.

b) The igniter relay is activated and provides ignition spark.

PROPANE

SSOV

NATURAL

GAS SSOV

TO AIR/FUEL

VALVE

MANUAL

SHUT-OFF

VALVE

PROPANE

GAS

INLET

NATURAL

GAS

INLET