CHAPTER 4: INITIAL START-UP

PR2: 04/22/13 Page 45 of 160


Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

BRASS HEX

HEAD CAP

(REMOVE TO

ACCESS GAS

PRESSURE

ADJUSTMENT

SCREW)

SSOV ACTUATOR

Figure 4-4: Gas Pressure Adjustment Screw Location

9. Set the ON/OFF switch to the ON position.

10.

Change the valve position to 34% using the ▲ arrow key. The unit should begin its start
sequence and fire.

11. Next, verify that the gas pressure downstream of the SSOV is 7.3” W.C. for both FM and

DBB (IRI) gas trains. If gas pressure adjustment is required, remove the brass hex nut
on the Natural Gas SSOV actuator containing the gas pressure adjustment (Figure 4-4).
Make gas regulator adjustments using a flat-tip screwdriver to obtain 7.3” W.C.

12. Increase the valve position to 100% and verify that the gas pressure downstream of the

SSOV remains at 7.2” W.C. Readjust pressure if necessary.

13. With the valve position at 100%, insert the combustion analyzer probe into the flue probe

opening and allow enough time for the combustion analyzer to settle.

14. Compare the measured oxygen level to the oxygen range for the inlet air temperature

shown in Table 4-1. Also, ensure that the carbon monoxide (CO) and nitrogen oxide
(NOx) readings do not exceed the values shown.

Table 4-1: Combustion Oxygen Levels for a

100%

Air/Fuel Valve Position

Inlet Air Temp

Oxygen %

± 0.2

Carbon Monoxide

NOx

>100°F

5.5 %

<100 ppm

<20 ppm

90°F

5.7 %

<100 ppm

<20 ppm

80°F

5.9 %

<100 ppm

<20 ppm

<70°F

6.0 %

<100 ppm

<20 ppm

15. If necessary, adjust the iris air damper shown in Figure 4-5 until the oxygen level is

within the range specified in Table 4-1.

16. Once the oxygen level is within the specified range at 100%, lower the valve position to

80%.

Advertising