CHAPTER 4: INITIAL START-UP

Page 52 of 160 PR2: 04/22/13

Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

40. The oxygen level at the 45% valve position should be as shown below. Also, ensure that the

carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.

Table 4-10: Combustion Oxygen Level at

45%

Valve Position

Oxygen %

± 0.2

Carbon Monoxide

NOx

7.0 %

<100 ppm

<100 ppm

41.

If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼ arrow
keys. This will adjust the output voltage to the blower motor as indicated on the display.

Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.

42. Once the oxygen level is within the specified range at 45%, press the ENTER key to store the

selected blower output voltage for the 45% valve position.

43.

Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.

44. Press the CHANGE key. SET Valve Position will begin to flash.

45.

Press the ▼ arrow key until the SET Valve Position reads 30%, then press the ENTER key.

46.

Press the ▼ arrow key until CAL Voltage 30% is displayed.

47. Press the CHANGE key. CAL Voltage 30% will begin to flash.

48. The oxygen level at the 30% valve position should be as shown below. Also, ensure that the

carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.

Table 4-11: Combustion Oxygen Level at

30%

Valve Position

Oxygen %

± 0.2

Carbon Monoxide

NOx

7.9 %

<100 ppm

<100 ppm

49.

If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼ arrow
keys. This will adjust the output voltage to the blower motor as indicated on the display.

Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.

50. Once the oxygen level is within the specified range at 30%, press the ENTER key to store the

selected blower output voltage for the 30% valve position.

51.

Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.

52. Press the CHANGE key. SET Valve Position will begin to flash.

53.

Press the ▼ arrow key until the SET Valve Position reads 21%, then press the ENTER key.

54.

Press the ▼ arrow key until CAL Voltage 21% is displayed.

55. Press the CHANGE key. CAL Voltage 21% will begin to flash.

56. The oxygen level at the 21% valve position should be as shown below. Also, ensure that the

carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.