Table 6-2: E8 Controller Fault Codes (Continued)

CODE

DESCRIPTION

EFFECT

CORRECTION

RESET

E 200

Communication Error HS1

Communications issue with BMM

0. Check all eBUS addresses

E 201

Communication Error HS1

Communications issue with BMM

1. Check all eBUS addresses

E 202

Communication Error HS1

Communications issue with BMM

2. Check all eBUS addresses

E 203

Communication Error HS1

Communications issue with BMM

3. Check all eBUS addresses

E 204

Communication Error HS1

Communications issue with BMM

4. Check all eBUS addresses

E 205

Communication Error HS1

Communications issue with BMM

5. Check all eBUS addresses

E 206

Communication Error HS1

Communications issue with BMM

6. Check all eBUS addresses

E 207

Communication Error HS1

Communications issue with BMM

7. Check all eBUS addresses

Internal Fault

E 81

E8: EEPROM fault. The

invalid value has been

replaced by the standard

value.