3.22.1 Important Factors for Terminal Orientation and Location

Terminals should be positioned so as to avoid products of combustion from entering openings into

the buildings or other vents.
The terminal should be located where dispersal of combustion products is not impeded and with

due regard for the damage or discoloration that might occur to building surfaces in the vicinity. In

certain weather conditions condensation may also accumulate on the outside of the air inlet pipe.

Such conditions must be considered and where necessary insulation of the inlet pipe may be

required. In cold and/or humid weather water vapor may condense when leaving the vent

terminal. The effect of such condensation must be considered. The terminal must be located in a

place not likely to cause a nuisance.
Maintain 12” of clearance above the highest anticipated snow level or grade, whichever is greater.

Please refer to your local codes for the snow level in your area.
The whole route of the vent system must be installed upwards and NEVER completely nor partly

downwards.

3.22.2 Minimum and Maximum Wall Thickness

The label at right, which is placed on the

unit,

indicates the minimum and maximum wall thickness

through which venting is allowed to penetrate
horizontally

. However, if venting is vertical, then there

is no minimum wall thickness.

3.23 Vent Pipe Sizing

The maximum length is the combined length of straight horizontal and vertical runs, and the

equivalent straight length of fittings. The required lengths for each boiler are as follows:

NOTE

The examples referenced in the table below are on the next page.

Table 3-4: MODULEX EXT Vent and Piping Diameter Chart

Model

No. of

Modules

Vent Diameter

Inches (mm)

Max. Vent Equiv.

Feet (M)

Examples 1 & 2

Max. Vent Equiv.

Feet (M)

Examples 3 & 4

EXT 1530

4

10” (254 mm)

100 ft. (30 m)

6 + 6 (1.8 + 1.8)

EXT 1912

5

10” (254 mm)

100 ft. (30 m)

6 + 6 (1.8 + 1.8)

EXT 2295

6

12” (304 mm)

100 ft. (30 m)

6 + 6 (1.8 + 1.8)

EXT 2677

7

12” (304 mm)

100 ft. (30 m)

6 + 6 (1.8 + 1.8)

EXT 3060

8

12” (304 mm)

100 ft. (30 m)

6 + 6 (1.8 + 1.8)

Table 3-5: MODULEX EXT Vent and Piping Length Chart

Model

Vent Pipe

Diameter

Sharp 90° Elbow

Equivalent

Feet (m)

Sweep 90° Elbow

Equivalent

Feet (m)

45° Elbow

Equivalent

Feet (m)

Maximum Length

Equivalent

Feet (Meters)

EXT 1530

10”

(254 mm)

13 Feet

(4 m)

7 Feet

(2 m)

5 Feet

(1.5 m)

100 Feet

(30 m)

EXT 1912
EXT 2295

12”

(304 mm)

13 Feet

(4 m)

7 Feet

(2 m)

5 Feet

(1.5 m)

100 Feet

(30 m)

EXT 2677
EXT 3060