8 burner / heat exchanger cleaning procedure, 9 heat and return sensor resistance values, Modulex ext – AERCO Modulex EXT 1530 - 3060 User Manual

Page 118

Advertising
background image

MODULEX EXT

1530, 1912, 2295, 2677, 3060 Boilers

Installation, Operation & Maintenance Manual

7.8 Burner / Heat Exchanger Cleaning Procedure

NOTE

AERCO recommends that periodic service be provided by qualified

technical personnel as often as required by the applicable rules and

regulations in force.

If the actual input (with the correct CO

2

levels) is within 5% of the value shown in section 3.33,

then the boiler does not need to be cleaned. The operation then can be limited to the cleaning of

the condensate siphon.
Dust and other particulate matter infiltrating into the combustion chamber over time will cause a

decrease of heating efficiency and output due to the buildup of combustion by-products onto the

thermally conductive surfaces. These surfaces must be cleaned from time to time in order to

return the unit to its original specifications for thermal efficiency and heat output.

NOTE

A reduction of the input can be caused by the obstruction of the

vent or air intake.

Before cleaning the boiler body sections, check the boiler input and the O

2

percentage (see

section 3.33).

7.9 Heat and Return Sensor Resistance Values

Nominal resistance differences at a given temperature ratio between the primary and return

heating sensors should be checked periodically by measuring the electrical resistance (ohms)

between the two sensors with a voltmeter. Use the chart below to determine the correct

resistance values at the given temperature ratios.

Table 7-2: Table of Resistance Values for Primary and Return Heat Sensors

°F

°C

Resistance (Ω)

32°

0°

32,755

50°

10°

20,003

68°

20°

12,571

86°

30°

8,112

104°

40°

5,363

122°

50°

3,627

140°

60°

2,504

152°

70°

1,762

176°

80°

1,263

194°

90°

920

Example: At 101 °F (25°C), the nominal resistance is 10067 Ohm. At 194 °F (90°C), the

nominal resistance is 920 Ohm

Page 118 of 138

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0095_0E

12/01/14

Phone: 800-526-0288

GF-139