MODULEX EXT

1530, 1912, 2295, 2677, 3060 BOILERS

Installation, Operation & Maintenance Manual

6.1.3 BCM (Boiler Communications Module) Fault Codes

The table below lists the fault codes and troubleshooting tips associated with the BCM.

Table 6-3: BCM Fault Codes

CODE

DESCRIPTION

EFFECT

CORRECTION

RESET

E 17

Boiler pipe is frozen.

Flow sensor temp. is

36°F or less.

Ignition is

inhibited. Pump

runs for 5 min at

max speed.

Carefully

defrost boiler.

AUTOMATIC - when Flow

sensor is greater than 41°F.

E 18

Maximum Δ-

temperature protection.

Flow temperature -

Return Temperature >

Water Δ-Temp

Protection + 50°F

All burners turned

OFF and Pump

ON at maximum

speed.

Check the

system

installation.

AUTOMATIC - when Δ-

temperature < Water Δ-

Temp Protection.

E 19

High outlet

temperature. Flow

sensor temperature >

203°F.

All burners turned

OFF and pump

ON at maximum

speed.

Check Flow

Sensor or

system pump.

AUTOMATIC - when Flow

sensor < 176°F.

E 37 BCM: Internal fault

E 38

Settings corrupted by

electromagnetic

interference.

Ignition is

inhibited. Pump

runs for 5 min at

max speed.

Re-program

the settings.

Contact

factory.

MANUAL - push reset

switch or cycle power.

E 56 BCM: No remote

control detected

E 57 BCM: No BMM

detected

E 58

BCM: Sensor global

flow detected.

Ignition is

inhibited.

Close request

input for

manual

operation.

MANUAL - push reset

switch or cycle power.