Installing the Pressure Relief Valve and Other Components – Continued

3. Connect the following components to the tapped holes in the manifold assembly (Figure 3-

6):

3/4” Pressure Relief Valve

Flow Switch

Pressure/Temperature Gauge

NOTE

It is important to next ensure that the flow switch is installed with the

“flow” arrow pointing in the direction of the flow.

4. Check to ensure that all components are securely tightened and that the flow switch

paddle moves freely without interference.

5. Locate the BMM module with the “FL” label (Figure 3-7), and remove the black jumper

wire from the terminals of the connector shown in the detail of Figure 3-7. Connect the two

flow switch wires to the two terminals. Flow switch wires have no polarity, so can be

inserted without regard to position.

Figure 3-7: BMM Location and Flow Switch Connection

3.13 Determination of Primary Boiler Pump or Boiler System Pump

The following table gives an indication of the pump’s flow rate in function of the

∆t

of the

primary circuit if the installation has a mixing header.
The size of the pumps must be determined by installers or technical engineers according to

boiler data and system design.

Remove this black jumper and

insert the two wires from the flow

switch into terminal connector.

DETAIL

OMM-0095_0E