MODULEX EXT

1530, 1912, 2295, 2677, 3060 BOILERS

Installation, Operation & Maintenance Manual

3.9 Gas Connection General Information

For

natural gas connections, refer to section 3.9.1. For propane gas connections, refer to

Section 3.9.2.
The gas supply connection must comply with local regulations or, if such regulations do not exist,

with the National Fuel Gas Code,

ANSI Z223.1/NFPA 54.

For Canada, the gas connection must comply with local regulations or, if such regulations do not

exist, with the

CAN/CSA-B149.1 - Natural Gas and Propane Installation Code.

Before installing the boiler it is recommended that all the supply piping be thoroughly cleaned in

order to remove any residual grime which could compromise the boilers correct functioning.
As a safety measure against gas leaks, AERCO recommends installing a surveillance and

protective system made up of a gas leakage detector combined with an on-off solenoid valve on

the gas supply line.
The boiler and its individual shutoff valve must be disconnected from the gas supply piping system

during any pressure testing of that system at test pressures in excess of 1/2 PSI (3.5kPa).
The boiler must be isolated from the gas supply piping system by closing its individual manual

shutoff valve during any pressure testing of the gas supply piping system at test pressures equal

to or less than 1/2 PSI (3.5 kPa).
Clause 1.34.1b.12: Provisions for combustion and ventilation air in accordance with the section

“Air for Combustion and Ventilation,” of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or

Sections 8.2, 8.3 or 8.4 of Natural Gas and Propane Installation Code, CAN/CSA B149.1, or

applicable provisions of the local building codes.
Clause 1.34.1b.21: A sediment trap must be provided upstream of the gas controls.

WARNING!

THE GAS CONNECTION MUST BE INSTALLED BY A

REGISTERED ENGINEER WHO MUST COMPLY WITH THE

REGULATIONS IN FORCE AND TO THE REQUIREMENTS

INDICATED BY THE LOCAL GAS SUPPLIER. AN INCORRECT

INSTALLATION CAN CAUSE INJURY OR DEATH TO

PERSONS, ANIMALS OR DAMAGE TO PROPERTY. THE

MANUFACTURER SHALL NOT BE HELD LIABLE FOR ANY

INJURY AND/OR DAMAGE DUE TO INAPPROPRIATE

INSTALLATION.
Do not use the boiler for another type of gas than indicated on the

identification plate of the boiler. This will cause improper functioning

and can damage the boiler. The suitable gas type for the boiler is

indicated on the packaging label and on the data plate boiler.First

check the identification plate on the boiler for the suitable gas type.
Always check the safety of the gas pipe system by means of a soap

bubble test using a leak-search spray.




OMM-0095_0E