3.38 Controls and Emergency Functions

Figure 3-34: MODULEX EXT Panel Controls and Indicators

ITEM

COMPONANT/FUNCTION

A

GLT (General Limit Thermostat): when enabled, it cuts the power supply to the

boiler and lights the warning lamp (Item D). To reset, remove the cap and push

the reset button.

B

Main Power Switch

C

Fuses: 1 = 6.3 A 2 = 10 A

D

Warning lamp of the Thermostatic

Lockout from GTL (General Limit Thermostat).

E

Main Switch

F*

Change-over Series/Parallel:

0 = Emergency is active or the control is managed by PLC or BMS.

I = Series connection (the cascade is managed by the BCM)

II = Parallel connection (condition of supply).

G*

In position “I” the plant will operate when requested at “CONSTANT SETPOINT”:

70°C –

Max heat output 50%.

H*

Enables burner reset in case of lock-out.

I*

YELLOW LED = Blinking = Communication between BMM and BCM is OK.

GREEN LED = ON = Active Pump

RED LED = ON = Failure Code Detected

*See section 4.2 for more information regarding the BCM (Boiler Communication Module).

NOTE

The emergency function enables the boiler’s burners to fire only at

50% and at 50°C in system return. All the system’s heating loads,

including the header pump, must be controlled manually.