MODULEX EXT

1530, 1912, 2295, 2677, 3060 BOILERS

Installation, Operation & Maintenance Manual

Disassembling the Boiler for Maintenance – Continued

6. Remove the rubber hoses (quantity depends on model) from bottom side of manifold

(highlighted in Figure 7-10), then lift entire manifold from the unit.

Figure 7-10: Removing Red Hoses and Manifold from Unit (Step 6)

7. Burner maintenance may be performed on all burner modules simultaneously or on each

one separately, as described in a) and b) below:

a)

All Modules: Use a 13mm wrench to remove all “A” and “C” nuts (surrounded by

horizontal dotted lines in Figure 7-11, below). Leave the “

B” screws affixed so all

burner plates may be lifted together. Then complete the remainder of the instructions

in this section.

b)

Separate Modules: Use a 13mm wrench to remove only the “A” and “C” nuts on

either side of the module in question (vertical dotted lines in figure 7-12), then

remove the “

B” Phillips screw at the end of the burner module. You can then skip the

remaining steps in this section and continue with section 11 - Cleaning the Burner

Module and Combustion Chamber.

Air Intake

Manifold

Remove

Hoses from under

Manifold

(one per module)

Lift out manifold after removing hoses.

OMM-0095_0E

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 121 of 138

GF-139

Phone: 800-526-0288

12/01/14