Step 2 — Place, Mount, and Rig the Unit —

When considering a location for the unit, be sure to consult

NEC (National Electrical Code, U.S.A.) and/or local code

requirements. Allow sufficient space for airflow, wiring, pip-

ing, and service. See Fig. 2-14.
NOTE: To facilitate refrigerant vent piping, all units have fus-

ible plugs with

1

/

4

in. SAE (Society of Automotive Engineers)

flares and pressure reliefs with

3

/

4

in. NPT fittings (if required

by local codes).
PLACING UNIT — Locate the unit so that the condenser

airflow is unrestricted both above and on the sides of the unit.

Airflow and service clearances are 6 ft (1.8 m) around the unit.

Acceptable clearance on the sides or ends without control boxes

can be reduced to 3 ft (1 m) without sacrificing performance as

long as the remaining three sides are unrestricted. Acceptable

clearance on the side with a control box can be reduced to 4 ft

(1.3 m) due to NEC regulations, without sacrificing performance

as long as the remaining three sides are unrestricted. Provide am-

ple room for servicing and removing the cooler. See Fig. 2-14 for

required clearances. Local codes for clearances take precedence

over the manufacturer’s recommendations when local codes call

for greater clearances.

If multiple units are installed at the same site, a separation of

10 ft (3 m) between the sides of the machines is required to

maintain proper airflow and minimize the chances of condens-

er air recirculation.
MOUNTING UNIT — The unit may be mounted on a level

pad directly on the base rails, on a raised mounting rail around

the unit, or on vibration isolation springs. For all units, ensure

placement area is strong enough to support unit operating

weight. See Tables 1A and 1B. Mounting holes are provided

for securing the unit to the pad, mounting rail or vibration

isolation springs. Bolt the unit securely to pad or rails. If vibra-

tion isolators (field-supplied) are required for a particular

installation, refer to unit weight distribution in Fig. 15A-15C to

aid in the proper selection of isolators. The 30XA units can be

mounted directly on spring isolators. Once installed, the unit

must be level to within

1

/

8

-in. per ft (1 cm per meter) along the

long axis of the oil separator. This is required for oil return to

the compressor(s).